Norma Trunk Fiber Cable

 

Features

  • Norma PRECONNECT trunk cable is compatible with fiber cores ranging from 8 to 144 for highdensity application.
  • Each PRECONNECT trunk cable end is installed with protection & pulling sleeves for crushrsistance, torsion-resistance,as well as water and dust proofing up to IP50 (indoor trunk). Up to 450N of pulling force can be applied to the PRECONNECT trunk cable.
  • PE, OFNR/Riser, OFNP/Plenum or LSZH sheathed fiber cables are available. LSZH rated fiber cable meets and passes IEC60332-1 and IEC60332- 3 requirements, OFNR rated cable meets and passes UL-1666 requirements, and OFNP rated cable meets and passes NFPA 262 requirements

 

Technical Parameters

  • Fiber type:OM2, OM3, OM4, OM5, G657A2, G652D
  • Sheathed type: LSZH, OFNR, OFNP
  • Connector insertion loss(Typical):
  • Single-mode 0.25dB(Low loss), multi-mode 0.25dB
  • (Low loss) Single-mode 0.6dB, multi-mode 0.5dB
  • Operation Temperature: -20Β°C~ 60Β°C
Parameter1Γ—122Γ—123Γ—124Γ—128Γ—1212Γ—121Γ—82Γ—83Γ—84Γ—86Γ—88Γ—812Γ—818Γ—8
Fan-out Length (mm)6006006006507508506006006006507007508501000
Divider Dimension (mm)16Γ—17Γ—105
Max. Tensile Force (Installation)660660660660800800450660660660660800800800
Min. Bending Radius (Install.) (mm)100100120120140180100100100120120140180180
Min. Bending Radius (Operation) (mm)5050606070905050506060709090
Crush Resistance (N/10cm)10001000100010001000100010001000100010001000100010001000
Temperature Range (Installation)-5Β°C to +50Β°C
Temperature Range (Operation)-20Β°C to +60Β°C

 

Applications

  • Used for fiber trunk connections between the MDA and IDA or HDA, as well as from HDA to ZDA or EDA